Details of new features & fixes across the ERACS versions.
The default three phase and single phase fault ratings are now set the same value according to voltage level as described below... - less than or equal to 0.415 kV = 31 MVA - less than or equal to 3.3 kV = 36 MVA - less than or equal to 6.6 kV = 72 MVA - less than or equal to 11 kV = 250 MVA - less than or equal to 33 kV = 1000 MVA - less than or equal to 66 kV = 2400 MVA - less than or equal to 132 kV = 4500 MVA - less than or equal to 275 kV = 15000 MVA - greater than 275 kV = 35000 MVA
This site or the third party tools it uses, make use of cookies needed to function and useful for the purposes indicated in the cookie policy. To learn more or deny consent, consult the cookie policy. By closing this banner, scrolling this page, clicking on a link or continuing to browse in another way, you accept the use of cookies.